General Information
NOTICE:
Warnings and Cautions
appear at appropriate sections
throughout this literature. Read
them carefully.
WARNING:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION:
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury. It
may also be used to alert against
unsafe practices.
CAUTION:
Indicates a situation that may result
in equipment or property-damage
only accidents.
Receiving
Upon receipt of the product, inspect
the shipping carton for signs of
visib
le damage. Report any damage
or shortage to the carrier, and note it
on the delivery receipt. Unit must be
stored in its original shipping carton
in a dry, secure place prior to its
installation and use.
WARNING
Hazardous Voltage w/
Capacitors!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury. Dischar
ge
all capacitors before servicing. Verify
with an appropriate voltmeter that
all capacitors have discharged.
Failure to disconnect power and
discharge capacitors before servicing
could result in death or serious
injury.
This power cord accessory can be
used to connect a PTAC unit to the
building power supply. See Table 1
for a description of available power
cord accessory kits.
230/208 Volt Electrical Supply
A power cord accessory installed on
230/208 volt model PTAC units can be
plugged into a receptacle mounted in
the wall, oor, or subbase. The
correct accessory is determined from
Table 1.
All wiring must be in accordance
with the NEC and local codes,
ordina
nces and regulations.
265 Volt Electrical Supply
The 265 volt model PTAC unit must
be permanently connected to the
building power supply in accordance
with the National Electrical Code. A
power cord accessory installed on a
265 volt model PTAC unit can be
plugged into a receptacle mounted in
the subbase (sold separately).
Subbase accessories provide an
enclosure for permanent connection.
Instructions provided with the
subbase must be carefully followed.
It is the responsibility of the installer
to ensure that connections are done
in accordance with these instructions
and all electrical codes.
The correct power cord accessory is
determined from Table 1. DO NOT
plug this power cord into a wall or
oor mounted electrical receptacle
and leave the cord exposed. This
type of connection is not
permitted
by the National Electric Code.